Rigging The Enclosure - Carrier 19XRV Series Start-Up And Service Instructions

With pic iii/pic 6 controls rockwell powerflex 755 vfd option
Table of Contents

Advertisement

When replacing the drive, reverse the procedures and tighten to
the torques for Frames 6 and 7 power terminal block listed in Ta-
ble 7.
Table 7 — Frames 6 and 7 Power Terminal Block
MAXIMUM LUG
FRAME
WIDTH
6
34.6 mm (1.36 in.)
7
43.5 mm (1.71 in.)
DRIVE RIGGING ACCESS
DRIVE WIDTH + 4 IN.
RECOMMENDED
TERMINAL
TORQUE
BOLT SIZE
·
11.3 N
m (100 in.-lb)
M8 x 1.25
·
11.3 N
m (100 in.-lb)
M8 x 1.25
FRONT VIEW
Fig. 22 — 19XRV Enclosure Access for Removing Drive

RIGGING THE ENCLOSURE

Where
overhead room and/or clearance in front of the drive en-
closure is insufficient to allow the drive to be safely removed from
the enclosure, the entire enclosure may have to be removed from
the chiller.
The dimensions and weights specified must be taken into consid-
eration when removing the enclosure. For 19XRV chillers, the to-
tal weight for Frames 6 and 7, including drive weight and enclo-
sure, is 720 lb. The 23XRV chiller enclosure, including all compo-
nents, weighs 975 lb. All lifting equipment and lifting components
(hooks, bolts, lifts, slings, chains, etc.) must be properly sized and
rated to safely lift and hold the weight of the enclosure and drive
while removing. See Fig. 24 and Fig. 25.
DRIVE RIGGING
ACCESS
2 IN.
SIDE VIEW
16
2 IN.
DRIVE POSITIONED FOR
VERTICAL LIFT
DRIVE EXTENDS
BEHIND MAIN
ENCLOSURE
SUPPORT FROM
BELOW