Configure The Vfd - Carrier 19XRV Series Start-Up And Service Instructions

With pic iii/pic 6 controls rockwell powerflex 755 vfd option
Table of Contents

Advertisement

Fig. 10 — Machine Nameplate
Fig. 11 — Drive Module Label

Configure the VFD

All configurations required by the VFD are supplied by the HMI
through the VFD Gateway. The 19XRV, 23XRV Std Tier VFD
can operate with PIC III and PIC 6. Any configuration changes
necessary and possible are made on the HMI screens. A complete
set of configurations is transmitted to the VFD each time the con-
trols are powered up.
Table 2 lists parameters displayed on the 19XRV, 23XRV PIC3/
VFD_CONF screen. Table 3 shows parameters in the Unit
Mounted VFD Configuration menu for PIC6. Parameters in ital-
ics are to be entered or confirmed at start-up. Parameters in bold
are to be changed only after consulting with Carrier service engi-
neering.
Table 2 — VFD Configurations (PIC3/VFD_CONF)
PARAMETER
MOTOR NAMEPLATE VOLTAGE
COMPRESSOR 100% SPEED
LINE FREQ=60 HZ? (NO=50)
RATED LINE VOLTAGE*
RATED LINE AMPS* †
RATED LINE KILOWATTS*
MOTOR RATED LOAD KW
MOTOR RATED LOAD AMPS
MOTOR NAMEPLATE AMPS
MOTOR NAMEPLATE RPM
MOTOR NAMEPLATE KW
INVERTER PWM FREQUENCY (0 = 4 KHZ, 1 = 2 KHZ)
SKIP FREQUENCY 1 (HZ)
SKIP FREQUENCY 2 (HZ)
SKIP FREQUENCY 3 (HZ)
SKIP FREQUENCY BAND LINE (HZ)
VOLTAGE % IMBALANCE
LINE VOLT IMBALANCE TIME (SEC)
LINE CURRENT % IMBALANCE
LINE CURRENT IMBAL TIME (SEC)
MOTOR CURRENT % IMBALANCE
MOTOR CURRENT IMBAL TIME
INCREASE RAMP TIME (SEC)
DECREASE RAMP TIME (SEC)
SINGLE CYCLE DROPOUT (DSABLE/ENABLE)
* Parameters marked with an * are not downloadable to the VFD but are used in
other calculations and algorithms in the ICVC.
NOTES:
1. Parameters in italics are to be entered or confirmed at start-up.
2. Parameters in bold are to be changed only after consultation with service
engineering.
Table 3 — VFD Configuration (PIC6/UM VFD
Configuration) CFGUMVFD - UM VFD Configuration
PARAMETER
COMPRESSOR 100% SPEED
RATED LINE VOLTAGE*
MOTOR NAMEPLATE CURRENT
MOTOR RATED LOAD CURRENT
MOTOR NAMEPLATE VOLTAGE
MOTOR NAMEPLATE RPM
MOTOR NAMEPLATE KW
SKIP FREQUENCY 1
SKIP FREQUENCY 2
SKIP FREQUENCY 3
SKIP FREQUENCY BAND
INCREASE RAMP TIME
DECREASE RAMP TIME
LINE VOLTAGE IMBALANCE%
LINE VOLT IMBALANCE TIME
LINE CURRENT IMBALANCE%
LINE CURRENT IMBAL TIME
MOTOR CURRENT IMBALANCE%
MOTOR CURRENT IMBAL TIME
SINGLE CYCLE DROPOUT
PWM SWITCH FREQUENCY (0=2 KHZ, 1=4 KHZ)
NOTES:
1. Parameters in italics are to be entered or confirmed at start-up.
2. Parameters in bold are to be changed only after consultation with service
engineering.
8
DEFAULT
VALUE
460
YES
460
200
100
100
200
100
3456
100
1
20.0
20.0
20.0
0.0
10
10
40
10
40
10
30
30
DSABLE
DEFAULT
VALUE
60
460
200
200
460
3000
1500
30
30
30
0
30
30
10
10
40
10
40
10
DISABLE
0