Carrier 19XRV Series Start-Up And Service Instructions page 13

With pic iii/pic 6 controls rockwell powerflex 755 vfd option
Table of Contents

Advertisement

Table 5 — Powerflex 755 Fault Code Descriptions and Corrective Actions (cont)
VFD
FAULT
ICVC
PIC6
CODE
FAULT
FAULT
ON VFD
STATE
STATE
HIST
SCREEN
15
206
449
17
216
446
20
206
449
21
225
445
24
204
442
33
206
449
36
286
438
38
39
220
432
40
41
42
220
449
43
44
206
432
45
206
432
46
206
432
55
NONE
444
61
206
449
62
206
449
64
206
449
77
206
449
78
206
449
79
206
449
80
206
449
87
206
449
91
206
449
93
206
449
94
206
449
95
206
449
96
206
449
97
206
449
100
206
451
106
284
453
107
NONE
451
113
206
451
124
206
451
FAULT TYPE
If this fault appears, there may be a prob-
Load Loss
lem with software configuration.
The DC bus ripple
has exceeded a
Line Voltage imbalance
preset level.
TorqPrv Spd Band
See VFD Fault Code 15
The current in one or more phases has
Output PhaseLoss
been lost or remains below a preset level.
The drive is not following a commanded
Decel Inhibit
deceleration because it is attempting to
limit bus voltage.
AuRsts Exhausted
See VFD Fault Code 15
The drive output current has exceeded
SW Overcurrent
the 1 ms current rating.
Phase U to Gnd
Phase V to Gnd
GROUND FAULT
Phase W to Gnd
Phase UV Short
Phase VW Short
GROUND FAULT
Phase WU Short
Phase UNot
Phase VNot
GROUND FAULT (no LF2 equivalent)
Phase WNot
Ctrl Bd Inverter
The temperature sensor on the main con-
Overtemp
trol board detected excessive heat.
Shear Pin 1
See VFD Fault Code 15
Shear Pin 2
See VFD Fault Code 15
Drive Overload
Drive is overloaded.
IR Volts Range
See VFD Fault Code 15
FluxAmpsRef
See VFD Fault Code 15
Rang
Motor did not come up to speed in the
Excessive Load
allotted time.
AutoTune Aborted
See VFD Fault Code 15
Ixo voltage calculated from motor name-
IXo VoltageRange
plate data is too high.
Pri VelFdbk Loss
See VFD Fault Code 15
HW Enable Check
See VFD Fault Code 15
Alt VelFdbk Loss
See VFD Fault Code 15
Aux VelFdbk Loss
See VFD Fault Code 15
PositionFdbkLoss
See VFD Fault Code 15
Auto Tach Switch
See VFD Fault Code 15
Parameter
The checksum read from the board does
Chksum
not match the checksum calculated.
The main control board did not recognize
Incompat MCB-PB
the power structure.
The main control board was moved to a
Replaced MCB-PB
different power structure. Data set to
default values.
Tracking DataErr
Internal data error
App ID Changed
Application firmware changed.
DESCRIPTION
To reset the processor, cycle power to chiller,
check VFD_CONF settings and save settings
when exiting VFD_CONF (PIC3)/CFGUMVFD
(PIC6) configuration screen.
Check VFD parameters with Drive Explorer.
Check phase-to-phase and phase-to-ground dis-
tribution bus voltage. Increase Line Voltage %
Imbalance in VFD_CONF (PIC3)/CFGUMVFD
(PIC6) screen.
See VFD Fault Code 15
Check Motor Current % Imbalance in VFD_CONF
(PIC3)/CFGUMVFD (PIC6) screen.
Verify input voltage is within drive specified
limits.
Verify system ground impedance follows proper
grounding techniques.
Disable bus regulation P186 and/or add dynamic
brake resistor and/or extend deceleration time
P537 and P538.
See VFD Fault Code 15
Check for excess load, improper DC boost set-
ting, DC brake volts set too high.
Check wiring between drive and motor.
Check motor for grounded phase.
Check motor terminals.
Replace drive.
Check wiring between drive and motor.
Check motor terminals.
Replace drive.
Check wiring between drive and motor.
Check motor terminals.
Replace drive.
Check that VFD refrigerant isolation valves are
open. Check VFD refrigerant strainer.
See VFD Fault Code 15
See VFD Fault Code 15
Check for high entering water temperature or low
condenser water flow. Check current settings in
VFD_CONF (PIC3)/CFGUMVFD (PIC6) screen.
See VFD Fault Code 15
See VFD Fault Code 15
Check that guide vanes are closed completely.
Check for high entering water temperature or low
condenser flow.
Repeat Autotune
See VFD Fault Code 15
Re-enter motor nameplate data in VFD_CONF
(PIC3)/CFGUMVFD (PIC6) screen.
See VFD Fault Code 15
See VFD Fault Code 15
See VFD Fault Code 15
See VFD Fault Code 15
See VFD Fault Code 15
See VFD Fault Code 15
Press ICVC reset (PIC3)/Reset alarm (PIC6).
Check VFD_CONF parameters.
Cycle power to the drive.
Flash with newer Application version software.
Press ICVC reset (PIC3)/Reset alarm (PIC6).
Check VFD_CONF (PIC3)/CFGUMVFD (PIC6)
parameters.
Cycle power to the drive.
Press ICVC reset (PIC3)/Reset alarm (PIC6).
Cycle power to the drive.
Verify application version.
13
CORRECTIVE ACTION