Siemens RDY2000BN Installation Instructions Manual page 9

Bacnet enabled commercial room thermostat
Table of Contents

Advertisement

Parameter
Definition
Heat Temp
P201
Limit
Cool Temp
P202
Limit
Temperature
Display
P203
Offset
Override
P204
Time Limit
Override
P205
Temp Limit
Heat Pump
P206
Compressor
Lock Out
Heat Pump
P207
Auxiliary
Heat Lockout
Service UV
P208
Lamp
Service
P209
Humidifier
Service Air
P210
Filter
Keypad
P211
Lockout
P212
Clock Format
Siemens Industry, Inc.
Table 4. 200 Series Parameters.
Display
Value Range
HEAT LIMIT
45 - 95
COOL LIMIT
50 - 95
TMP OFFSET
-5 to +5
"---" = unlimited;
0 = none;
2 =2 hours;
4 = 4 hours;
6 = 6 hours;
HRS OVR RD
8 = 8 hours
10 = 10 hours
12 = 12 hours
24 = 24 hours
96=96 hours
---
1
2
3
4
5
TMP OVR RD
6
7
8
9
10
OFF
15=15°F
20=20°F
25=25°F
HP COMP LO
30=30°F
35=35°F
40=40°F
45=45°F
OFF
40=40°F
45=45°F
HP AUX LO
50=50°F
55=55°F
60=60°F
UV LAMP
0-365
HMDFR
0-365
SRVC
FLTR SRVC
0-365
OFF
2
KEY LOCK
3
12
CLOCK
24
Default
Extended Definition
Sets maximum allowable heating
95°F
setpoint
Sets minimum allowable cooling set
50°F
point
Enables adjustment of control temp and
display temp in 1-degree increments.
0°F
Applies only to onboard temp sensor.
Indoor temp only.
Number of hours that scheduled
2
setpoint can be manually overridden.
0 = no override allowed
Number of degrees F that are allowed
above or below scheduled setpoint.
---
--- = Unlimited
Heat pump compressor will not operate
OFF
below this outdoor temp -- forcing unit
to auxiliary heat
Heat pump auxiliary heat will not
OFF
operate above this outdoor temp.
Number of days until SERVICE UV
0
LAMP message is displayed.
0 = function disabled.
Number of days until SERVICE
HUMIDIFIER message is displayed.
0
0 = function disabled.
Number of days until SERVICE AIR
FILTER message is displayed.
0
0 = function disabled.
OFF = No lockout
2 = Partial Lockout (only temp setpoint
OFF
can be adjusted)
3= Total Lockout
12 = 12-hour format
12
24 = 24-hour format
Document No. 125-1009
Installation Instructions
February 10, 2020
Notes
~ Does not appear if HEAT
STAGES = 0
~ Does not appear if COOL
STAGES = 0
~ Do not adjust until in
operation for at least 1 hour.
~ This parameter does not
appear if SCHEDULER =
OFF
~ This parameter does not
appear if SCHEDULER =
OFF
~ Only shown if SYS TYPE =
HP with AUX HEAT and there
is an outdoor temp sensor
~ Must be lower than HP
AUX LO
~ Only shown if SYS TYPE =
HP with AUX HEAT and there
is an outdoor temp sensor
~ Must be higher than HP
COMP LO
Page 9 of 20