Siemens RDY2000BN Installation Instructions Manual page 11

Bacnet enabled commercial room thermostat
Table of Contents

Advertisement

Parameter
Definition
Temperature
P306
Input 2 Type
Temperature
P307
Input 2 Low
Temperature
P308
Input 2 High
Configurable
P309
Input 3 (IN3)
Temperature
P310
Input 3 Type
Temperature
P311
Input 3 Low
Temperature
P312
Input 3 High
Configurable
P313
Input 4 (IN4)
Temperature
P314
Input 4 Type
Temperature
P315
Input 4 Low
Temperature
P316
Input 4 High
Aux Output 1
P317
(OUT1)
Siemens Industry, Inc.
Value
Display
Range
1
TMP IN 2
2
-58 --
+250F
TMP 2 LO
-50 ---
+120C
-58 --
+250F
TMP 2 HI
-50 ---
+120C
1
2
3
4
5
INPUT 3
6
7
8
9
OFF
1
TMP IN 3
2
-58 --
+250F
TMP 3 LO
-50 ---
+120C
-58 --
+250F
TMP 3 HI
-50 ---
+120C
1
2
3
4
5
INPUT 4
6
7
8
9
OFF
1
TMP IN 4
2
-58 --
+250F
TMP 4 LO
-50 ---
+120C
-58 --
+250F
TMP 4 HI
-50 ---
+120C
1
2
3
AUX OUT 1
4
5
OFF
Default
Extended Definition
1 = Type 2 Thermistor
1
2= 0-10V
Calibrates thermostat to low end of
0
temp sensor signal (e.g., 0V = -40°F)
Calibrates thermostat to high end of
120
temp sensor signal at 10 volts (e.g.,
10V = 250°F)
1 = Indoor Temperature (Remote)
2 = Indoor Temperature (Average)
3 = Supply Temp
4 = Return Temp
5 = Outdoor Temp
OFF
6 = Humidity (0-10V)
7 = CO2 (0-10V)
8 = Occupancy (DI)
9 = Fault
OFF = Not Used
1 = Type 2 Thermistor
1
2 = 0-10V
Calibrates thermostat to low end of
0
temp sensor signal (e.g., 0V = -40°F)
Calibrates thermostat to high end of
120
temp sensor signal at 10 volts (e.g.,
10V = 250°F)
1 = Indoor Temperature (Remote)
2 = Indoor Temperature (Average)
3 = Supply Temp
4 = Return Temp
5 = Outdoor Temp
OFF
6 = Humidity (0-10V)
7 = CO2 (0-10V)
8 = Occupancy (DI)
9 = Fault
OFF = Not Used
1= Type 2 Thermistor
1
2= 0-10V
Calibrates thermostat to low end of
0
temp sensor signal (e.g., 0V = -40°F)
Calibrates thermostat to high end of
temp sensor signal at 10 volts (e.g.,
120
10V = 250°F)
1 = Humidification
2 = Dehumidification
OFF
3 = Occupied
4 = Air Quality
5 = Economizer Enable
OFF = Not Used
Document No. 125-1009
Installation Instructions
February 10, 2020
Notes
~ Only appears if INPUT 2 =
1/2/3/4/5
~ SCW can be 0 or 1
Only appears if TMP IN 2 = 1
Must be lower than TMP 2 HI
Only appears if TMP IN 2 = 1
Must be higher than TMP 2
LO
~ Cannot have duplicate
selections for inputs 1-4
~ If set to 9 (fault), a DI here
causes SERVICE
REQUIRED segment to
activate
~ Only appears if INPUT 3 =
1/2/3/4/5
Only appears if TMP IN 3 = 1
Must be lower than TMP 3 HI
Only appears if TMP IN 3 = 1
Must be higher than TMP 3
LO
~ Cannot have duplicate
selections for inputs 1-4
~ If set to 9 (fault), a DI here
causes SERVICE
REQUIRED segment to
activate
Only appears if INPUT 2 =
1/2/3/4/5
~ Only appears if TMP IN 4 =
1
~ Must be lower than TMP 4
HI
~ Only appears if TMP IN 4 =
1
~ Must be higher than TMP 4
LO
~ Cannot have duplicate
selections for outputs 1-3
~ Air Quality not an option
unless an input is set to CO2
sensor
~ If system is conventional
with 3H +3C, AO1 will default
to, and be locked as, stage 3
cooling.
Page 11 of 20