Document No. 125-1009
Installation Instructions
February 10, 2020
Dehumidification
Parameters
P317/ P318/P319: One of these must be set to 2
P320: NO (default) = Dehumidification will only
occur if there is a call for cooling. YES =
Dehumidification relay will be energized
independently of heating and cooling relays.
Dehumidity Setpoint: User adjustable to desired
level in dehumidification mode.
Sensors: Onboard humidity sensor or optional remote
humidity sensor.
The dehumidification relay will energize when measured
humidity rises approximately 4% above setpoint and will
de-energize when measured humidity reaches setpoint.
Deadbands and proof timers are in force to prevent short
cycling.
Economizer Enable
Parameters
P317/P318/P319: One of these must be set to 5.
P301/P305/P309/P313: One of these must be
set to 8 if the optional occupancy sensor is used.
Sensors: None required, however an optional occupancy
sensor can be used instead of, or in conjunction with the
scheduler to determine occupancy.
The Economizer Enable relay will be energized
whenever a cooling relay is energized or the space is
occupied. The thermostat uses the scheduled Comfort
mode to determine if the space is occupied.
An optional occupancy sensor can also be used for
definitive proof of occupancy.
An output configured for Occupancy Notification can also
be used for Economizer Enable.
Pre-Purge
Parameters
P317/P318/P319: One of these must be set to 5.
P403
Sensors: None required.
To enable the economizer and energize the fan relay
prior to scheduled occupancy, set P403 to the number of
hours before scheduled occupancy for pre-purge to
begin. This function requires a schedule to be
configured.
Page 16 of 20
Occupancy Notification
Parameters
P301/P305/P309/P313: If the optional occupancy
sensor is used, one of these must be set to 8.
P317/P318/P319: To signal an external device that
the space is occupied, one of these must be set to 3
P404: If the optional occupancy sensor is used,
P404 can be used to set a minimum run timer for
any actions that are activated by occupancy, such
as Economizer Enable, control to occupied
temperature setpoints, and so on. Note that many
occupancy sensors also have onboard proof timers.
There are two primary methods by which the thermostat
can assume the space is occupied.
1. The space is assumed to be occupied when the
schedule mode is set to Comfort.
2. During periods in which the schedule indicates
the space is unoccupied, any human interaction
with the thermostat (for example, setpoint
adjustment) will put the thermostat into
Occupied mode.
The optional occupancy sensor can be used in
conjunction with the schedule. The thermostat will follow
the assumptions above, but an input from the occupancy
sensor during a scheduled unoccupied period will put the
thermostat in the Occupied mode for the duration of the
timer set in P404.
To utilize the Occupancy functions, the thermostat must
have an active schedule.
Air Quality Management
Parameters
P301/P305/P309/P313: One of these must be
set to 7.
P317/P318/P319: One of these must be set to 4.
P402: CO2 Setpoint
Sensors: Optional CO2 Sensor
If measured CO2 exceeds setpoint by 200 PPM
for a minimum of 60 seconds, the Air Quality
output and fan relays will be energized. The
minimum run time is 5 minutes.
When measured CO2 falls below setpoint and
appropriate minimum run time has been met, the
Air Quality output relay will be de-energized and
the fan relay shall revert to normal operation.