Document No. 125-1009
Installation Instructions
February 10, 2020
Parameter
Definition
P601
MS/TP MAC address
P602
Baud Rate
P603
Device Instance
P604
Max Master
P605
Serial number
P606
Max Info Frames
Parameter
Definition
P701
Firmware
Page 14 of 20
Table 8. 600 Series BACnet Configuration Parameters*.
Display
MS--TP MAC
BAUD RATE
DEV ID
MAX MASTER
SER NR
MAX FRAME
CAUTION:
* See the Energy Management System Network Plan before entering values in
the RDY2000BN 600 Series BACnet Configuration Parameters. Incorrect values
will prevent connection to the Energy Management System.
Table 9. 700 Series BACnet Configuration Parameters
Display
FIRMWARE
Value Range
Default
0-255
255
A
= Auto
9.6
= 9600
19.2 =19200
38.4 = 38400
A=Auto
57.6 = 57600
76.8 = 76800
115.2 =115200
0 - 4194303
4194303
1--127
127
Display
Display Only
Only
1-- 10
1
Value Range
Default
Display only
Display only
Extended Definition
MS/TP MAC address must be unique for the
entire network 1 to 254.
In systems that support and use Master Nodes
valid range to use is from 1 to 127.
In systems that support and are using auto
discovery leave value at default 255
NOTE: When integrating with APOGEE
this parameter to be a Master Node.
This parameter will set the network's baud rate.
Auto value will match detected Baud Rate in
systems that support and are using auto
discovery leave value at default "A"
Device Instance (unsigned integer 0-4194303)
In systems that support and are using auto
discovery leave value at default 4194303
Max Master
Display Serial number, 10 digit hex,
programmed in factory
Max Info Frames
Extended Definition
Display Firmware Version
Siemens Industry, Inc.
®
, set