Siemens RDY2000BN Installation Instructions Manual page 20

Bacnet enabled commercial room thermostat
Table of Contents

Advertisement

Document No. 125-1009
Installation Instructions
February 10, 2020
Parameter
P502
Interstage Differential - Cooling
P503
Cooling Minimum Off Time
P504
Cooling Minimum On Time
P505
Changeover Delay
P506
Cooling Deadband
P507
Interstage Delay - Heating
P508
Interstage Differential - Heating
P509
Heating Minimum Off Time
P510
Heating Minimum On Time
P511
Heating Deadband
P601
MS/TP MAC address
P602
P603
P604
P605
P606
P701
P911
Page 20 of 20
Definition
Baud rate
Device instance
Max master
Serial number
Max info frames
Firmware
Expert Password
Default
1°F (0.5°C)
5
3
10
1°F
5
Conv. = 1°F (0.5°C); HP = 2°F (1°C)
5
3 (10 if heat pump)
1°F (0.5°C)
255
A = Auto
4194303
127
Display only
1
Display only
Current PW
Field Value
Siemens Industry, Inc.