4. Connect the cable assembly (p/n 3-0500-122) from the modem's J4
connector to the computer's host port (TB16 on the main board) or
other RS232 device. If connecting to TB16, return the main board and
mounting bracket to the down position. Connections to TB16 are
shown in the table below.
Table 8–5. 212A modem cable assembly to TB16 connections
Cable Assembly Color
Green/Shield
White
Blue
Violet
Brown
Yellow
Black
Orange
Red
5. J5 is the modem's power connector. Using the 20 AWG wire provided,
connect J5 to TB1 on the enclosure door panel as shown below.
Table 8–6. 212A modem power to TB1 connections
Color
Red
Black
6. Connect a standard miniature six-position RJ11C telephone plug
(customer supplied) to the phone line connector on the modem (J6).
7. If necessary, return the main board and mounting bracket to the down
position, tighten the thumbscrews, and shut the enclosure door.
TB16 on Main Board
TB16-8 (GND)
TB16-1 (RX)
TB16-2 (CTS)
TB16-3 (TX)
TB16-4 (RTS)
TB16-5 (DCD)
TB16-6 (+12V)
TB16-7 (V
)
BO
TB16-9 (+5V)
J5 on 212A Modem
PWR
GND
AutoPILOT PRO Flow Computer User Guide 8-3
212A Modem Option
Installation
TB1 on Enclosure Door
TB1 positions 1–3 (POS)
TB1 positions 4–6 (NEG)