Step 6: Setting The Hardware Configuration Of Pc Stations On The Es - Siemens SIMATIC PCS 7 BOX Manual

Hide thumbs Also See for SIMATIC PCS 7 BOX:
Table of Contents

Advertisement

5.1.6
Step 6: Setting the Hardware Configuration of PC Stations on
the ES
Once you have configured your PCS 7 project in the SIMATIC Manager on the
external ES, you have to add communication CPs in HW Config on both PC
stations and a WinCC application on the PC station of the ES.
Note
Use the CP 5611 module for production operation either on the external ES or on
the SIMATIC PCS 7 BOX station depending on the connection of the PDM.
The following section describes the integration of the CP 5611 in the external ES.
Requirements
The ES has been added to your PCS 7 project.
The PCS 7 project is displayed in the component view of the SIMATIC
Manager.
Follow These Steps:
1. Double-click on the SIMATIC PC station containing the CPU 416-2 PCI in the
left window of the SIMATIC Manager. The objects of the SIMATIC PC station
are then displayed in the right window.
2. Double-click on the "Configuration" object.
3. In HW Config, navigate to the CP IE General in the hardware catalog under
SIMATIC PC Station > CP Industrial Ethernet.
Press the left mouse button and drag the marked CP IE General to the slot in
the station window that you selected in the Component Configurator on the
SIMATIC PCS 7 BOX station. Click on the "OK" button in the displayed dialog.
4. Double-click on the SIMATIC PC station representing the ES in the left window
of the SIMATIC Manager. The objects of the SIMATIC PC station are then
displayed in the right window.
5. Double-click on the "Configuration" object.
6. In HW Config, navigate to the CP IE General in the hardware catalog under
SIMATIC PC Station > CP Industrial Ethernet.
Press the right mouse button and drag the marked CP IE General to the slot in
the station window that you selected in the Component Configurator on the ES.
Click on the "OK" button in the displayed dialog.
Process Control System PCS 7 - PCS 7 BOX
A5E00272813-01
Additional Commissioning and Configuration
5-7