4.2
Configuring SIMATIC PCS 7 BOX for a Single Station
System
4.2.1
Step 1: Configuring the PC Stations Using the Commissioning
Wizard
The SIMATIC NET Commissioning Wizard is automatically started when the
SIMATIC PCS 7 BOX station is first booted.
Requirements
Installation of SIMATIC PCS 7 V6.0 SP3
Software WinAC 3.4 for SIMATIC S7 CPU 416-2 PCI
Note
The Windows 2000 Professional Hardware Wizard may appear during the
commissioning of all the hardware adapters (CP 5611, CP 1512, CPU 41x2 PCI).
Close this Wizard when any new hardware is detected.
Follow These Steps:
Note
The required settings in the SIMATIC NET Commissioning Wizard is described in
detail in the manual PC Configurations and Authorizations. The following
procedures relate specifically to the special features of the SIMATIC PCS 7 BOX.
1. Start the SIMATIC PCS 7 BOX station.
2. The SIMATIC NET Commissioning Wizard starts. Go to the next dialog of the
Wizard by pressing the "Next" button.
3. Use the on-board CP 5611 module for your PCS 7 project by activating the
option "Use module in configured PC station for production".
Specify the slot in the "Index" field. Slots (index) 1 and 3 cannot be used
because they will be used later by the WinCC application and the CPU 41x-2
PCI when the PCS 7 project is created . Otherwise, accept all other default
settings.
4. If the CP 1512 module is installed, it will be recognized by the SIMATIC NET
Commissioning Wizard. It is not needed in the "single station system"
configuration variant. Therefore, activate the option "Use module for
programming only" for this module.
4-2
Process Control System PCS 7 - PCS 7 BOX
A5E00272813-01