Additional Commissioning and Configuration
5.2.5

Step 4: Configuring NetPro

The employed modules are assigned to networks and connections are made in
NetPro on the ES. A PROFIBUS DP must also be inserted. This is connected with
DP interface of the CPU 416-2 PCI in the SIMATIC PCS 7 BOX station.
Using PDM
For the configuration variant "SIMATIC PCS 7 BOX in the PCS 7 network", the
access from the PDM to intelligent field devices connected to the PROFIBUS DP
can be made via the PCS 7 network or the SIMATIC BOX station.
connection pathfrom an ES in a PCS 7 Network
The OS in the SIMATIC PCS 7 BOX station is accessed via the terminal bus using
the TCP/IP protocol. This connection path is not configured in NetPro but it must be
physically present.
Access to the CPU 416-2 within the SIMATIC PCS 7 BOX Station
The AS in the SIMATIC PCS 7 BOX station is accessed via the plant bus using the
ISO protocol. This connection route is configured in NetPro an it must be physically
present.
Requirements
The hardware has been configured in HW Config on the ES.
The PCS 7 project is displayed in the component view of the SIMATIC
Manager on the ES.
Follow These Steps:
1. In the SIMATIC Manager, open the NetPro by selecting the menu command
Options > Configure network.
2. Insert the PROFIBUS DP in your network view from the catalog under
Subnets by double-clicking on this object.
3. Select the CP 5611 in the SIMATIC PCS 7 BOX station and drag it onto the
PROFIBUS you have just inserted. Release the mouse button there.
In the "Properties" dialog, check if a free PROFIBUS address is specified. If it
is not, you can enter an address by clicking on the "Properties" button in the
"Interface" section of the "Properties" dialog.
4. Select the DP interface in the SIMATIC PCS 7 BOX station and drag it onto the
PROFIBUS you have just inserted. Release the mouse button there.
5. Select the IE General in the SIMATIC PCS 7 BOX station and drag it onto the
Industrial Ethernet. Release the mouse button there.