Huawei SmartACU2000D Series User Manual page 31

With no pid module
Hide thumbs Also See for SmartACU2000D Series:
Table of Contents

Advertisement

SmartACU2000D Smart Array Controller
User Manual (with No PID Module)
Table 2-5 Cables to be prepared in the fiber ring network scenario
No.
Cable
1
Three-phase AC
power cable
2
(Optional)
Peripheral
network cable
3
Peripheral
RS485
communications
cable
4
Cabinet PE
cable
5
Optical cable
6
Single-phase
AC power cable
7
(Optional) 24 V
DC output
power cable
Issue 01 (2020-02-14)
Recommended Model or Specifications
Three-core (L1, L2, and L3) outdoor armored
copper cable
When the rated AC voltage on the LV side of
the transformer station is less than or equal to
600 V, the operating voltage between the
three-phase AC power cable and the ground
should be greater than or equal to 600 V.
When the rated AC voltage on the LV side of
the transformer station is greater than 600 V
and less than or equal to 800 V, the operating
voltage between the three-phase AC power
cable and the ground should be greater than or
equal to 1000 V.
Cat 5e outdoor shielded network cable with an
outer diameter of less than 9 mm (0.35 in.) and
internal resistance of less than or equal to 1.5
ohms/10 m (1.5 ohms/32.81 ft), as well as
shielded RJ45 connectors
Computer cable (DJYP2VP2-22 2x2x1) or
armored shielded twisted pair that can be used
outdoors, as well as OT-M4 terminals
Outdoor copper cable and OT-M6 terminals
Four-core or eight-core single-mode armored
optical cable with a transmission wavelength of
1310 nm and an outer diameter of less than or
equal to 18 mm (0.71 in.)
Standard connection: two-core outdoor
armored copper cable
Connection through a tube: single-core
outdoor copper cable
Operating voltage to the ground ≥ 300 V
Standard connection: two-core outdoor
armored copper cable
Connection through a tube: single-core
outdoor copper cable
Operating voltage to the ground ≥ 300 V
Copyright © Huawei Technologies Co., Ltd.
2 Overview
Cross-sectional Area
Range of the Cable
(Recommended Value)
2
2
8–10 mm
(10 mm
8 AWG
-
2
2
0.5–1 mm
(1 mm
)
20–18 AWG (18 AWG)
2
2
6–16 mm
(16 mm
10–6 AWG (6 AWG)
-
2
2
4–6 mm
(4 mm
)
12–10 AWG (12 AWG)
2
2.5–4 mm
(2.5 mm
14–12 AWG (14 AWG)
)
)
2
)
24