YASKAWA SI-P3/V Technical Manual page 35

Yaskawa ac drive-v1000 option, profibus-dp
Hide thumbs Also See for SI-P3/V:
Table of Contents

Advertisement

DPV0 PNU
Number
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Note: When PNU is set to 0 and INDEX is set to MEMOBUS/Modbus register number, V1000 parameter values can be read and
written instead of using PNU number.
Note: MEMOBUS/Modbus register C1-01 is 200Hex
When PNU is 0 and INDEX is 200H(512 dec), C1-01 setting value can be read and written instead of using PNU 31(dec) and
INDEX 01.
Example: Writing to C1-01
Command Setting
Data type
PKE
IND
PWE
STW
HSW
Response
Data type
PKE
IND
PWE
STW
HSW
Example: Reading d1-17
Command Setting
Data type
PKE
IND
PWE
STW
HSW
Response
Data type
PKE
YASKAWA ELECTRIC SIEP C730600 23B V1000 Option PROFIBUS-DP Technical Manual
Description
0028H MEMOBUS/Modbus #
0029H MEMOBUS/Modbus #
002AH MEMOBUS/Modbus #
002BH MEMOBUS/Modbus #
002CH MEMOBUS/Modbus #
002DH MEMOBUS/Modbus #
002EH MEMOBUS/Modbus #
002FH MEMOBUS/Modbus #
0030H MEMOBUS/Modbus #
0031H MEMOBUS/Modbus #
0032H MEMOBUS/Modbus #
0033H MEMOBUS/Modbus #
0034H MEMOBUS/Modbus #
00FFH MEMOBUS/Modbus #
Settings
701FH
1
10
Settings
401FH
1
0
Settings
6029H
11H
0
Settings
4029H
8 Parameter Process Data Object Formats
Description
7: Change parameter setting value from array
1FH = 31 (C1 parameter)
C1-01
Assign 10
Up to Master command
Up to Master command
Description
4: Transfer parameter value (array word)
1FH = 31 (C1 parameter)
C1-01
N/A
Up to drive status
Up to drive status
Description
6: Request parameter value from Array
29H = 41 (d1 parameter)
11H = 17 (d1-17)
N/A
Up to Master command
Up to Master command
Description
4: Transfer parameter value (array word)
29H = 41 (d1 parameter)
INDEX
40
41
42
43
44
45
46
47
48
49
50
51
52