YASKAWA SI-P3/V Technical Manual page 27

Yaskawa ac drive-v1000 option, profibus-dp
Hide thumbs Also See for SI-P3/V:
Table of Contents

Advertisement

IND
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
PWE
Bit
0 to 31
STW/ZSW
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
<1> This is the setting value for d1-17 in drives running software version 2102 and later. The software version appears on the drive nameplate,
indicated by "PRG".
YASKAWA ELECTRIC SIEP C730600 23B V1000 Option PROFIBUS-DP Technical Manual
PPO Write
Sub-Index for parameter number
PPO Write
Setting Data
PPO Write
OFF1: reserved
OFF2: reserved
OFF3: reserved
Enable to RUN
0: Baseblock + Stop
1: Not Baseblock
0: STOP
1: RUN
Ramp function generation enable: reserved
Enable ramp function generator set-point: reserved
1: Fault Reset
0: Stop
1: JOG RUN forward (Fmax/10 speed)
0: Stop
1: JOG RUN reverse (Fmax/10 speed)
0: Local control
1: Control from PROFIBUS
Reserved
8 Parameter Process Data Object Formats
Reserved
Error code when Response ID is 7
0: Incorrect PNU number
1: Write mode error
2: Lower or upper limit violated
3: Disabled IND is set
17: Write mode error during Uv condition or Write mode error during
parameter processing
<1>
<1>
PPO Read
Sub-Index for parameter number
Reserved
PPO Read
PPO Read
Ready to switch on: always 1
Ready: always 1
0: Not ready
1: Drive ready
0: No fault condition
1: Fault condition
Always 1
Always 1
Switch-on inhibit: always 0
0: No alarm condition
1: Alarm condition
0: No speed agree
1: Speed agree condition
0: Local control
1: Control from PROFIBUS
Always 0
27