04/99

Editing a block

Now open the LAD/STL/FBD editor by double-clicking on the newly created Function FC1 in the
SIMATIC MANAGER.
Click on Title next to the block number FC1 and assign the block name Belt control.
Now give the first network the name Initial position. To do this, click on the entry Title next to
the network number.
Click in the gray field below the line Network 1 : to activate it. Enter a network comment in this field:
There must be no parcel on the belt.
Below the network comment you can now insert your program lines. To do this, click in the white area
below the gray comment field. This opens a box with the current cursor position. When making your
entry, make sure you include the relevant blanks (at least one blank each as a separator between
operation code, operand and comment) in each program line, otherwise STEP 7 will not recognize the
instruction and will signal this in red italics. Insert the following in the first network:
FC1: Belt control
Network 1 : Initial position
AN
DB1.DBX0.0
AN
DB1.DBX1.0
A
DB1.DBX0.1
=
M 15.0
To insert a new network, click on
your system.
Getting Started with C7-621-AS-i
// Opto_Bero : no parcel
// Position switch: no parcel
// Ejector in initial position
// Initial position
in the toolbar. In this network, program the operating status of