3.2

Environmental Specifications

Before installing the XLS, confirm that the intended location conforms to the
environmental specifications listed in
Parameter
Ambient temperature
Temperature gradient
(maximum)
Relative humidity
(non-condensing)
Wet bulb temperature
Altitude
Table 3-3 Environmental specifications
To prevent interference with the optical barcode reader, light curtain
sensors, and cartridge present sensors, do not install the XLS in areas
exposed to direct sunlight.
3.3

Power Requirements

The XLS operates from the single-phase alternating current power sources (mains) shown
in
Table
3-4.
Rated Line
Voltage
100–240 VAC
Table 3-4 XLS mains requirements
The base library includes a 20-amp switch/circuit breaker. (Power is connected to the base
library only; the MEM2 cabinet gets its power from the base library.) Other than selecting
the appropriate AC power cord (see
changes to operate from any input voltage within the rated line voltage.
XLS Library Site Planning Guide
Table
3-3.
Operating
+5°C to +32°C
(+41°F to +90°F)
1°C/minute, 10°C/hour
(2°F/minute, 18°F/hour)
20% to 80%
26°C (79°F) maximum
–1000 to +10,000 feet
–304.8 to +3,048 meters
CAUTION
Maximum
Operating Line
Operating Line
Voltage
264 VAC
Section 3.3.1 on page
3
Installing the Library
Non-operating
–20°C to +60°C
(–4°F to +140°F)
1°C/minute, 20°C/hour
(2°F/minute, +36°F/hour)
10% to 90%
29°C (84°F) maximum
–1,000 to +40,000 feet
–304.8 to +12,192 meters
Minimum
Line Frequency
Voltage
105 VAC
3-8), the XLS requires no
Range
48–62 Hz
3-7