Specifications
Model Name (Combination Unit)
Model Name (Independent Unit)
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor Output×Number
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Gas Pipe
Pipes
Oil Equalizing Pipe
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator
Oil
Charge Volume
Standard Accessories
Drawing No.
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
18
RXYQ38MY1B
RXYQ10MY1B+RXYQ12MY1B+RXYQ16MY1B
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Ivory White (5Y7.5/1)
mm
(1600×930×765)+(1600×1240×765)+(1600×1240×765)
Cross Fin Coil
Hermetically Sealed Scroll Type
m³/h
(13.72+10.47)×2+(13.72+10.47+10.47)
r.p.m
(6480, 2900)×2+(6480, 2900×2)
kW
(2.7+4.5)+(4.2+4.5)+(3.0+4.5+4.5)
Propeller Fan
kW
m³/min
180+210+210
Direct Drive
φ19.1 (Brazing Connection)
mm
φ41.3 (Brazing Connection)
mm
φ6.4 (Flare Connection)
mm
kg
230+281+325
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
%
kg
9.6+11.4+14.4
Electronic Expansion Valve
Synthetic (ether) oil
L
(1.9+1.6)+(1.9+1.6)+(1.9+1.6+1.6)
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038966B, 4D038967C, 4D038969C
difference : 0m.
difference : 0m.
: 0m.
95,000
374,000
109
106
102,000
407,000
119
Soft start
0.75×3
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
4~100
R410A
Installation Manual, Operation Manual, Connection Pipes,
Clamps
RXYQ40MY1B
RXYQ10MY1B+RXYQ14MY1B+RXYQ16MY1B
101,000
397,000
117
113
109,000
433,000
127
Ivory White (5Y7.5/1)
(1600×930×765)+(1600×1240×765)+(1600×1240×765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.47)+(13.72+10.47+10.47)×2
(6480, 2900), (6480, 2900×2)×2
(2.7+4.5)+(2.0+4.5+4.5)+(3.0+4.5+4.5)
Soft start
Propeller Fan
0.75×3
180+210+210
Direct Drive
φ19.1 (Brazing Connection)
φ41.3 (Brazing Connection)
φ6.4 (Flare Connection)
230+323+325
Deicer
4~100
R410A
9.6+12.9+14.4
Electronic Expansion Valve
Synthetic (ether) oil
(1.9+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6)
4D038966B, 4D038968C, 4D038969C
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
SiE39-404
Specifications