SiE39-404
Troubleshooting
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the wiring
YES
adaptor for electrical
appendices
connected?
NO
YES
Is the schedule
timer connected?
NO
Are
there two or
more optional
controllers
YES
for centralized control
connected with the
connector for setting
master
control?
NO
Reset the power supply for
all optional controllers for
centralized control
simultaneously.
Troubleshooting (OP: Schedule Timer)
Is a data station
connected?
NO
Is a parallel interface
connected?
NO
Is the schedule
timer's individual/combined
connector connected?
NO
If the malfunction is still not cleared:
Cannot be used in
combination with a wiring
adaptor for electrical
appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and data
station cannot be used in
combination. Disconnect
YES
either the schedule timer or
data station and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and parallel
interface cannot be used in
combination. Disconnect either
YES
the schedule timer or parallel
interface and reset the power
supply for all optional
controllers for centralized
control simultaneously.
Disconnect the schedule
timer's individual / combined
YES
connector and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Arrange so that the connector
for setting master control is
connected to one controller
for centralized control and
reset the power supply for all
optional controllers for
centralized control
simultaneously.
Disconnect the connector for
setting master control from
the master controller, connect
to another optional controller
for centralized control and
simultaneously reset all
optional controllers for
centralized control again. The
controller connected by the
connector for setting master
control when the malfunction
is cleared is defective and
must be replaced.
(V2839)