Daikin VRV II RXYQ5MY1B Service Manual page 39

R-410a heat pump 50hz
Hide thumbs Also See for VRV II RXYQ5MY1B:
Table of Contents

Advertisement

Specifications
Slim Ceiling Mounted Duct Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
H6 Sound Level (H/L)
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
H4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 External static pressure is changeable to set by the remote controller this pressure means "High static
H6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
28
FXDQ20NVE
kcal/h
2,000
Btu/h
7,900
kW
2.3
kW
2.2
kcal/h
2,200
Btu/h
8,500
kW
2.5
Galvanized Steel Plate
mm
200×900×620
mm
2×12×1.5
0.176
Sirocco Fan
W
62×1
m³/min
9.5/7.5
Pa
44-15 H5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
mm
VP20
mm
(External Dia. 26 Internal Dia. 20)
kg
26
dBA
33/29
Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
difference: 0m.
difference: 0m.
0m. (Heat pump only)
pressure - Standard static pressure".
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
FXDQ25NVE
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
200×900×620
2×12×1.5
0.176
Sirocco Fan
62×1
9.5/7.5
44-15 H5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
φ6.4 (Flare Connection)
φ12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
3D045744
SiE39-404
FXDQ32NVE
3,150
12,500
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
200×900×620
2×12×1.5
0.176
Sirocco Fan
62×1
10.5/8.5
44-15 H5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
φ6.4 (Flare Connection)
φ12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications