Troubleshooting by Indication on the Remote Controller
3.45 " U7 "
Indoor Unit: Malfunction of Transmission Between
Outdoor Units
U7
Remote
Controller
Display
Applicable
All models of indoor units
Models
Method of
Microcomputer checks if transmission between outdoor units.
Malfunction
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed
Causes
204
Improper connection of transmission wiring between outdoor unit and external control
adaptor for outdoor unit
Improper connection of transmission wiring between outdoor units.
Improper cool/heat selection
Improper cool/heat unified address (outdoor unit, external control adaptor for outdoor unit)
Defect of outdoor unit PC board (A1P)
Defect of external control adaptor for outdoor unit
Si39-502A
Troubleshooting