Engineering; Fuse Protection Against Short-Circuits; Derating Rated Operational Current (Ems - Eaton EMS-SWD Series Manual

Electronic motor starter
Table of Contents

Advertisement

Available languages

Available languages

2 Engineering

2.1 Fuse protection against short-circuits

2.2 Derating rated operational current (EMS-...-SWD)
Fuse protection against short-circuits can be added to a three-phase supply
system in one of the following ways:
Table 4: Fuse protection EMS-...SWD for IEC applications
Protective
I
q
device
16A gG/gL
50 kA
30A CCMR 30
50 kA
FAZ-B16/3
2.5 kA
PKM0-4
50 kA
PKM0-6.3
15 kA
Table 5: Fuse protection EMS-... for UL applications
Protective
SCCR
device
20A RK5
5 kA
30A Class CC
100 kA
DANGER
The electronic motor starter must be replaced after a short-
circuit occurs. It is strictly prohibited to keep using it!
Depending on the installation situation and the maximum ambient air
temperature, it may be necessary to derate the maximum rated operational
current.
Derating is based on the following installation situations:
separate mounting,
connected in series with 30 mm clearance,
without clearance.
Electronic motor starter EMS-...-SWD 12/18 MN034002ZU-DE/EN www.eaton.com
2.1 Fuse protection against short-circuits
Voltage
Type of
coordination
500 V
1
500 V
1
400 V
1
415 V
1
415 V
1
Voltage
Type of
coordination
480 V
480 V
2 Engineering
51

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents