3.4 GATEWAY SETTINGS

RS485-ETH-N can be worked as a server or client. Gateway Settings tab is divided into two sub
sections independently from Server or Client Mode.
„ MODBUS Request Side (interface in which information will be requested from RS485-ETH-N).
„ MODBUS Response Side (interface in which RS485-ETH-N will make queries).
NOTE: If the option "Validate MODBUS data" is not active, the data flow is carried out using the communication
protocol of the existing system.
When the "Validate MODBUS data" option is active, data flow is allowed if it communicates with the MODBUS
protocol during data transfer. If the protocol is not MODBUS, communication will not take place.
Default gateway settings of RS485-ETH-N are as follows:
MODBUS REQUEST SIDE
MODBUS RESPONSE
SIDE
Figura 3.6: Gateway Settings
MODE OF
PHYSICAL
OPERATION
PORT
Server
Ethernet
Server
Serial
Tabela 3.3: Default Gateway Settings of RS485-ETH-N
PROTOCOL
PORT
Modbus TCP
502
Modbus RTU
-
Ethernet / Serial Gateway - RS485-ETH-N | 17
www.weg.net
TIMEOUT
10000 msec
1000 msec