APPENDIX K - LIST OF PARAMETERS (WITH RANGES AND DEFAULT VALUES)

Menu item
Sub item / Parameter
Boiler Parameters
(1) CH Mode
(3) CH Setpoint
(185) Calc. Setp. Offset
(109) MN Climate Curve Comp
(110) CH Min Setpoint
(111) CH Max Setpoint
(5) Boiler Pump Overrun
(6) Flue Temp Limit
(7) CH Hysteresis Up
(112) CH Hysteresis Down
(9) Anti Cycle Period
(10) Anti Cycle Temp Diff
(12) Hx Diff ΔT Maximum
(13) Hx Diff Max Wait Time
(14) Max Power CH
(15) Min Power CH
(16) CH PID P
(17) CH PID I
(18) CH PID D
(19) Design Supply Temp
(20) Design Outdoor Temp
(21) Baseline Supply Temp
(22) Baseline Outdoor Temp
(23) Design Supply Min Limit.
(24) Design Supply Max Limit
(25) Warm Weather Shutdown
(26) Boost Temp. Increment
(27) Boost Time Delay
(28) Night Setback Temp.
(35) DHW Mode
(113) Max Power DHW
(114) Min Power DHW
(36) DHW Tank Hyst Down
(37) DHW Tank Hyst Up
(38) DHW Tank Supply Extra
(39) DHW Tank Supp Hyst Dn
(40) DHW Tank Supp Hyst_Up
(41) DHW Tank Hold Warm
(42) DHW Priority
(43) DHW Max Priority Time
(44) DHW Pump Overrun
(45) DHW Tank PID P
(46) DHW Tank PID I
(47) DHW Tank PID D
(48) DHW/Tank Setpoint
(115) DHW Store Setpoint
(49) DHW Hysteresis Down
(50) DHW Hysteresis Up
(51) DHW Instant PID P
Range
0...5
30...90
-10...10
-10...10
20...50
50...90
0...900
10...120
0...20
0...20
10...900
0...20
10...60
10...250
50...100
1...30
0...1275
0...1275
0...1275
30...90
-25...25
30...90
0...30
4...82
27...90
0...35
0...30
1...120
0...30
0) Disabled
1) Tank + sensor
2) Tank + thermostat
50...100
1...30
0...20
0...20
0...30
0...20
0...20
0...10
On (DHW), Off (CH), Time
1...255
0...900
0...1255
0...1255
0...1255
40...71
40...71
0...20
0...20
0...1255
57
57
Default Value
Units
0
70
°C
0
°C
0
°C
30
°C
80
°C
60
Sec.
100
°C
5
°C
5
°C
120
Sec.
16
°C
40
°C
30
Sec.
100
%
1
%
100
250
0
80
°C
0
°C
40
°C
20
°C
30
°C
80
°C
22
°C
0
°C
20
Min.
10
°C
0
100
%
1
%
5
°C
5
°C
15
°C
5
°C
5
°C
5
°C
On
30
Min.
60
Sec.
100
500
0
50
°C
57
°C
4
°C
4
°C
100
SHUTDOWN
APPENDIX
User level
2: Installer
1: User
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
3: Factory
2: Installer
2: Installer
2: Installer
2: Installer
3: Factory
3: Factory
2: Installer
2: Installer
3: Factory
3: Factory
3: Factory
1: User
1: User
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
2: Installer
3: Factory
3: Factory
3: Factory
2: Installer
2: Installer
2: Installer
3: Factory
3: Factory
3: Factory
1: User
1: User
3: Factory
3: Factory
3: Factory