APPENDIX
SHUTDOWN
Vent terminals
Vent terminals
Air intake
Multiple air and vent horizontal termination:
X ≥ 12" (305 mm);
Y ≤ 25" (635 mm)
Z = 12" to 16" (305 mm to 406 mm)

APPENDIX J - SENSOR RESISTANCE

SENSOR RESISTANCE TABLE
Y
Temperature °F (°C)
Testing tolerance ±10%
32 (0)
41 (5)
Z
50 (10)
59 (15)
68 (20)
77 (25)
86 (30)
95 (35)
104 (40)
113 (45)
X
122 (50)
131 (55)
140 (60)
149 (65)
158 (70)
167 (75)
176 (80)
185 (85)
194 (90)
203 (95)
212 (100)
221 (105)
230 (110)
239 (115)
248 (120)
257 (125)
Resistance table for:
− Heat exchanger supply temperature sensor
− Heat exchanger return sensor
− Heat exchanger flue sensor
− Boiler supply sensor
− System temperature sensor
− Outdoor temperature sensor
56
56
Resistance [Ω]
27396
22140
17999
14716
12099
10000
8308
6936
5819
4904
4151
3529
3012
2582
2221
1918
1663
1446
1262
1105
970
855
755
669
594
529