INSTALLATION
4.12.5 Adjusting and Setting O
− Insert a combustion analyzer probe into the test port
shown in Fig. 15
− Go to the Touchscreen and access the Module screen (as
described on "6.3.4 Module Screen" page 32) relevant to
the module under analysis;
− Press "MODULE TEST" button;
− Press "HIGH POWER" button.
Wait 2 or 3 minutes to reach steady state conditions and record
the O
value.
2
Test port of
the module
Fig. 15 Test Port for Combustion Analysis (available on each
individual heat exchanger)
To adjust the O
value at the maximum power turn the screw "A"
2
(rotate counter-clockwise to decrease O
type wrench is necessary for this adjustment.
Verify that the value of O
2
indicated in the following table (be careful to make small changes
and confirm that the value is stable before making additional
adjustment).
Press "LOW POWER": the fan will run at the minimum speed.
Fig. 16 O
Adjustment
2
To adjust the O
value at the minimum input, turn the screw "B"
2
(rotate clockwise to decrease O
Verify that the value of O
2
indicated in the following table (be careful to make small changes
and confirm that the value is stable before making additional
adjustment).
Press "Reset" and the boiler return to the "stand by" mode.
Repeat the above process for all heat exchangers.
Limits
2
) shown in Fig. 16, allen
2
is stable and is within the range
Screw "A"
Screw "B"
) shown in Fig. 16.
2
is stable and is within the range
Array Combustion Values
Gas Type
Natural Gas
LP Gas

4.13 AC Electrical Power Wiring

External AC power connections are made to the unit inside the
electrical box, located on the inside of the front doors. Open the
front doors and remove the panel mounted in the upper part of
the left front door of the unit as shown in Fig. 16.
Left Door
Cover Panel
Service
Display
Fig. 17 Front Doors Internal Layout
Loosen the screws of the cover and remove panel to access the
internal connections shown in Fig. 18.
20
Max. Fire O
%
Min. Fire O
2
4.2 – 5.8
4.2 – 5.8
5.4 – 10.2
5.4 – 10.2
Right Door
Cover Panel
%
2