Chapter 5 : Installation Procedure

Chapter 5 : Installation Procedure

5.1 Rack Mounting

You can rack-mount the UPS and the Delta lithium-ion battery pack RT-20K-LIB
in a standard 19-inch server rack. The UPS and the Delta lithium-ion battery
pack RT-20K-LIB should adopt the same mounting kits and mounting
procedures. The instruction below only shows the rack mounting of the Delta
lithium-ion battery pack RT-20K-LIB, if you want to check the rack mounting of
the UPS, please refer to the Delta Amplon RT Series UPS User Manual.
1. Attach the bracket ears provided in the package to the lateral mounting holes
of the Delta lithium-ion battery pack RT-20K-LIB. See Figure 5-1.
(Figure 5-1: Mount the Bracket Ears)
2. Follow step ❶ to ❹ to install the Delta lithium-ion battery pack RT-20K-LIB in
Delta's rail kit (optional). See Figure 5-2.
Step ❶ : Adjust the length of the rails according to your rack.
Step ❷ : Tighten the rails' nuts.
Step ❸ : Fix the rails on your rack.
Step ❹ : Insert the Delta lithium-ion battery pack RT-20K-LIB in your rack and
tighten the provided screws.