Setting Switches On Sw1 - Allen-Bradley 1203 Series User Manual

Remote i/o communications module
Table of Contents

Advertisement

Setting Switches on SW1

Address
Switch Setting Address
Decimal Octal
8 <---- 3
0
0
111111
1
1
011111
2
2
101111
3
3
001111
4
4
110111
5
5
010111
6
6
100111
7
7
000111
8
10
111011
9
11
011011
10
12
101011
11
13
001011
12
14
110011
13
15
010011
14
16
100011
15
17
000011
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com
Setting the Rack Address
DIP switches 8 through 3 on SW 1 set the rack address for the
Remote I/O module. Each Remote I/O device must have a rack
address that the controller can recognize. Each rack contains 8 words.
Important: When using a PLC-2 family processor, add 1 to the rack
number set on the Remote I/O module DIP switches to
your PLC code. The PLC-2 cannot have a Remote I/O rack
numbered zero, so add a value of one to the rack number
value when writing your PLC code.
Figure 2.12
To edit the rack address, you need to:
1. Refer to the following table to determine the settings for SW1.8
through SW1.3:
Switch Setting Address
Decimal Octal
8 <---- 3
16
20
111101
17
21
011101
18
22
101101
19
23
001101
20
24
110101
21
25
010101
22
26
100101
23
27
000101
24
30
111001
25
31
011001
26
32
101001
27
33
001001
28
34
110001
29
35
010001
30
36
100001
31
37
000001
Important: Not all controllers support all of these node addresses.
Refer to the documentation for your controller. The
maximum number of devices on a Remote I/O link is 32.
2. Slide the switches to their appropriate positions.
Settings take effect when a module or board first receives power.
When you change a setting, you must remove and then reapply power
for the new setting to take effect.
Configuring the Module
Rack Address Switches
Off = 0
On = 1
Use DIP switches 8 through 3 on SW1
for setting the module address.
Switch Setting Address
Decimal Octal
8 <---- 3
32
40
111110
33
41
011110
34
42
101110
35
43
001110
36
44
110110
37
45
010110
38
46
100110
39
47
000110
40
50
111010
41
51
011010
42
52
101010
43
53
001010
44
54
110010
45
55
010010
46
56
100010
47
57
000010
2–13
Switch Setting
Decimal Octal
8 <---- 3
48
60
111100
49
61
011100
50
62
101100
51
63
001100
52
64
110100
53
65
010100
54
66
100100
55
67
000100
56
70
111000
57
71
011000
58
72
101000
59
73
001000
60
74
110000
61
75
010000
62
76
100000
63
77
000000

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: