Setting Switches On Sw2 - Allen-Bradley 1203 Series User Manual

Remote i/o communications module
Table of Contents

Advertisement

Setting Switches on SW2

Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com
Figure 2.7
Truncate Last Datalink Switch
Off = 0
On = 1
Use SW 3.8 for truncating the
last datalink.
To set the truncate last datalink feature, you need to:
1. Refer to the following table to determine the setting for SW 3.8:
Duplicate Message Detection
Disable
Enable
2. Slide the switch to its appropriate position.
3. If the switch is enabled, cross out the second module group
(word) of the last datalink in your I/O image table on page 2–4.
Settings take effect when a module or board first receives power.
When you change a setting, you must remove and then reapply power
for the new setting to take effect.
Setting the Starting Group
SW 2.2 and SW 2.1 set the starting group. A starting group is the
word in a rack at which the group starts. The starting group depends
on the rack size. To determine the starting group, you must set the
switches on SW3 and calculate the rack size. A full rack is 8 words.
For example, if we enabled the switches for Logic Command/Status,
Reference/Feedback, and datalink A, we use 4 words in the rack, so
we need a 1/2 rack. Using the table below as a guide, we could set the
starting group for word 0, 2, or 4 for our example.
Figure 2.8
Starting Group Switches
Off = 0
On = 1
Use SW 2.2 and SW 2.1
for setting the starting group.
To edit the starting group, you need to:
1. Refer to the following table to determine starting groups that you
can use:
Rack Size
Starting Group
1/4
0, 2, 4, or 6
1/2
0, 2, or 4
3/4
0 or 2
Full
0
Configuring the Module
SW 3.8
0
1
2–9