Chapter 6 Troubleshooting
6.1

Error indications of EH-RMP2

Error indications of EH-RMP2 are shown below.
LED
RDY
PROFIBUS
EH-RMP2
RDY
RUN ERR
STATUS
REM
STATUS
PROFIBUS
EH-RMP2
RDY
RUN ERR
STATUS
REM
RUN
PROFIBUS
EH-RMP2
RDY
RUN ERR
STATUS
REM
ERR
PROFIBUS
EH-RMP2
RDY
RUN ERR
STATUS
REM
Table 6.1-1 Error Indications of EH-RMP2
Indicate pattern
Hardware error
OFF
Power supply error
Lit in red
Hard ware error
OFF
Power supply error
Flash in red
Internal error
WDT error
Lit in red
Side DIP switch
setting error
Side DIP switch
Fifth-flash in green
setting error
Forth-flash in green
Link parameter error
Triple-flash in green
Configuration data error
Double-flash in green
CPU module error
Single-flash in green
Initialization
No communication
OFF
established
Slave units at least one are
Blinking
not established
All slave units are not
Lit
established
Description
・Check power of power supply module
・Replace EH-RMP2
Replace EH-RMP2
Check power of power supply module
Replace EH-RMP2
・Replace EH-RMP2
・Check the side DIP switch.
Check the side DIP switch.
Check the address of sending data area of
CPU module.
・Check the connection of the communication
cable
・ Configure correct data with use of the
SYCON.net
Clear error of the CPU module
Set the I/O assignment of the CPU module.
・Check the connection of the communication
cable
・Check system and node address and push
reset switch of EH-RMP2
・Check the connection of the communication
cable
・Check system and node address and push
reset switch of EH-RMP2
・Check the connection of the communication
cable
・Check system and node address and push
reset switch of EH-RMP2