Ingeteam INGECON SUN STORAGE 1Play Installation And Configuration Manual page 22

Stand-alone system
Hide thumbs Also See for INGECON SUN STORAGE 1Play:
Table of Contents

Advertisement

Available languages

Available languages

Installation and configuration of a stand-alone system
5. Configure the GRID reading.
Click on the Grid icon and configure the Power Meter Id parameter with the name
provided to the previously configured ISS 1Play.
From the pop-up window in Device Type select the type: PV/Battery Inverter.
Select the connection type: Ethernet.
IP: IP address acquired by the inverter
Port: 502
Modbus node: 01
Alias: ISS 1Play
Phase: R
SOC maximum: This value is informative. Not used for the monitoring strategy.
Set the same value as the INGECON SUN STORAGE 1Play as SOC MAX.
SOC minimum: Not used for the monitoring strategy. Set the same value as the
INGECON SUN STORAGE 1Play as SOC MIN.
Click on Find . If the unit is correctly connected and configured a warning is
displayed with the device's serial number and firmware.
Finally, save the settings by clicking on Save .
Ingeteam

Advertisement

Chapters

Table of Contents
loading

Table of Contents