HOMEOWNER
Annual Inspection
Have the fireplace inspected annually before use.
More frequent inspection and cleaning may be required if the
fireplace is installed in an area exposed to pet hair or dust,
or to excessive lint from new carpeting or bedding materials.
During The Annual Checkup, The Technician Will:
Inspect the pilot (flame safety system) and burner(s) for
proper operation and replace any damaged parts.
Check the glass and gasket for proper seal.
Vacuum and clean any foreign debris in the firebox that is
not supposed to be there.
Clean Glass with a suitable fireplace glass cleaner. Abrasive
cleaners must not be used. Be careful not to scratch the
glass when cleaning.
Check the barrier screen for fit and structural integrity. See
Pages 82 and 83.
Check all latches or other door retention components for
proper operation, tension, and relief mechanisms are free
from obstructions. See Pages 82 and 83.
Inspect the log set (if applicable) and decorative media (if
applicable) for debris or damage.
Freshen up the glowing embers if applicable.
Replace batteries in the remote transmitter and receiver if
applicable.
Inspect the venting and vent termination cap for damage,
corrosion, sooting, or obstruction and correct if present.
In addition, clean and inspect the fireplace following any
remodeling work in your home.
39357-0-1018

MAINTENANCE AND SERVICE

INSTALLER
Annual Inspection
Have the fireplace inspected annually before use.
More frequent inspection and cleaning may be required if the
fireplace is installed in an area exposed to pet hair or dust,
or to excessive lint from new carpeting or bedding materials.
During The Annual Checkup, The Technician Will:
Inspect the pilot (flame safety system) and burner(s) for
proper operation and replace any damaged parts.
Test and measure the flame failure response time of the
flame safety system. It must de-energize the safety shut-off
in no more than 30 seconds.
Vacuum and clean any foreign debris in the firebox that is
not supposed to be there.
Inspect and ensure that the lighting of the main burner
occurs within 4 seconds of the gas valve opening. Visual
inspection should match the information illustrated in the
manual. Inspect primary air openings for blockage.
Check the glass and gasket for proper seal.
Clean Glass with a suitable fireplace glass cleaner. Abrasive
cleaners must not be used. Be careful not to scratch the
glass when cleaning.
Check all latches or other door retention components for
proper operation, tension, and relief mechanisms are free
from obstructions. See Pages 82 and 83.
Check the barrier screen for fit and structural integrity.
See Pages 82 and 83.
Inspect the log set (if applicable) and decorative media
(if applicable) for debris or damage.
Freshen up the glowing embers if applicable.
Replace batteries in the remote transmitter and receiver
if applicable.
Inspect the venting and vent termination cap for damage,
corrosion, sooting, or obstruction and correct if present.
Check all accessible gas-carrying tubes, connections,
pipes and other components for leaks.
In addition, clean and inspect the fireplace following any
remodeling work in your home.