Installation and configuration of a photovoltaic self consumption system with batteries
Therefore, after connecting the Ethernet cable to the router, the EMS Board will automatically
obtain an IP address.
Ingeteam recommends configuring the EMS Board with a fixed IP address. This
way its operation does not depend on a DHCP server.
For further information about "changing the IP address", please see "INGECON
SUN EMS Board: Configuration Manual" , available on the Ingeteam website.
3.5.3 External Wattmeter
By default, the wattmeter has already been configured with Modbus node number 01 and
"single phase" AC type of grid.
No extra configuration is required for the wattmeter.
For more information about the configuration of the External Wattmeter, please
see the " INGECON SUN EMS Board: Configuration Manual" , available on the
Ingeteam website.
3.6 System device firmware update
The firmware of all the Ingeteam devices in the system (energy manager, EMS, communication
cards, inverters, etc.) should be updated to the latest available version on the Web:
www.ingeteam.com.
3.7 Configuration of the installation via the INGECON SUN EMS Tools
software
This section describes the steps required to configure the installation from the PC INGECON
SUN EMS Tools application.
For more information about configuration of the INGECON SUN EMS Tools,
please see the " INGECON SUN EMS Board: Configuration Manual" , available on
the Ingeteam website.
1. Creation of a new installation or plant
Enter the information requested.