3.4.2 External Wattmeter
The external wattmeter used is the EM24-DIN.AV9.3X.IS.P. This must be installed in the main
panel of the dwelling in order to measure both the total consumption of the installation and the
photovoltaic generation and batteries of the ISS 1Play.
The energy consumption measured by the wattmeter is sent to the EMS Board via the RS-485
communication.
Proceed as follows:
1. Wattmeter electrical connection:
2. Connection of RS-485 wiring for communication with the EMS Board:
3. Fit the end-of-line resistor (120 Ω) between connection 42-41 for a correct RS-485
communication.
AAX2026IQM25_B.docx
Installation and configuration of a photovoltaic self consumption system with batteries
Connection
11
1
4
3
Connection
42
41
43
Signal
Grid Neutral
Grid Phase Input
Bridge 1-4
Grid Phase Output
Signal
RS-485 B (+)
RS-485 A (-)
GND
35