Configure Ddm800; Restart System - Tyco MX Series Service And Maintenance Instructions

Addressable fire controllers
Table of Contents

Advertisement

3.13.3.4 SINGLE DEVICE POLL MODE
When selected, this option allows a single device to be
polled continuously.
Press 6 from the Diagnostics menu, select the Loop and
Point to be polled then press Enter. The following type of
screen will be displayed:
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Press F4 to start the device poll, F5 will change to End.
Press F5 to end the device poll.
3.13.3.5 CHANGE ADDRESS
When selected, this option allows the address of a device to
be changed.
Press 7 from the Diagnostics menu. The following type of
screen will be displayed:
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
New
Use the '>>', '-' and '+' keys to select the options. Press
Enter when all options have been selected.
CAUTION:
DO NOT SELECT A NEW ADDRESS THAT IS
ALREADY BEING USED ON THE LOOP.
© 2009 Tyco Safety Products
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
Single Device Poll
Zone 002
B002
South Building
1st Floor Corridoor
Room 117
801 H
Start
Change Address
Loop :
B
Old Address :
017
Type : 801H
New Address :
025
-
+
Enter
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
3.13.4
CALIBRATE DDM800
This option is used to calibrate a DDM800 when monitoring
a conventional detection circuit using diode bases.
CAUTION:
THIS OPTION SHOULD ONLY BE USED
UNDER THE FOLLOWING
CIRCUMSTANSES:
1) ON INITIAL COMMISSIONING WHEN THE
CIRCUIT TO BE MONITORED HAS ALL ITS
DETECTORS FITTED.
2) WHEN CHANGES HAVE BEEN MADE TO
DETECTOR TYPES, ADDITIONAL
DETECTORS OR WIRING CHANGES.
Press 4 from the Service Menu, the following screen will be
displayed:
MX Panel
Fri, 01-Aug-08
14:15
Company Name
General
Back
>>
Select the Panel( if networked), Loop and Point address of
the DDM800 to be calibrated, pressing F5 will store the
returned current value for the DDM800.
3.13.5

RESTART SYSTEM

Press 5 from the Service Menu, the following screen will be
displayed:
MX Panel
Thu, 26-Jan-09
00:01
Company Name
General
Back
Pressing 1 will restart the system.
MX/MZX
17A-04-S
17
10/09
Calibrate DDM800
Panel:
Loop:
All
Point:
All
+
Enter
-
Restart System
1 - Restart Panel
PAGE 27 of 40
01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mx2Mzx seriesMzx125

Table of Contents