Huawei FusionModule500 User Manual page 145

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Maintenance area
Camera
The Intelligent
Battery Monitoring
System
Issue 07 (2019-12-20)
Item
Network interface
indicator
Monitor interface
(network
management system
or Web)
Cable connections
Camera availability
Battery management
alarm
Copyright © Huawei Technologies Co., Ltd.
Operation
N/A
N/A
N/A
N/A
On the camera
WebUI, choose
Playback, and
specify values Start
time, End time,
and Record type
for the camera to be
queried. Then, click
Query and you can
view the video in
real time.
N/A
Expected Result Troubleshooting
blinking green.
see
Troubleshooting the
Monitoring System
to rectify the fault.
The green
Check the network
indicator is steady
cable connection.
on, and the
yellow indicator
is blinking.
Export smart
If an alarm is
cooling product
generated by
logs, alarms,
referring to Alarm
temperature,
References or
humidity, as well
contact Huawei
as the operating
technical support.
status and time of
the water sensor,
door status
sensor,
temperature
sensor, and
smoke sensor
from the
monitoring
system. View the
historical alarms
generated in this
quarter and select
the most common
five ones.
The cable
Secure loose cables.
connections are
secure.
Cables are not
Replace damaged
damaged.
cables.
The video is
If the monitoring
displayed
video is not
normally.
displayed, check
that the IP address
is correctly set, and
check cable
connection or
replace the camera.
For details, see
4.5.3.4 Replacing a
Camera.
No battery
Find the cause of an
management
alarm based on the
alarm is
alarm information.
4 Maintenance
4.4.2
136

Advertisement

Table of Contents
loading

Table of Contents