Kimo CO 110 Technical Data Sheet

Kimo CO 110 Technical Data Sheet

Co transmitter
Hide thumbs Also See for CO 110:

Advertisement

Quick Links

CO transmitter
CO 110

KEY POINTS

- Range from 0 to 500 ppm
- 0-10 V active output, power supply 24 Vac/Vdc (3-4 wires) or 4-20 mA output, passive loop,
power supply from 16 to 30 Vdc (2 wires)
- ABS V0 housing, IP65 (depending on model), with or without display
- "¼ turn" system mounting with wall-mount plate
- Housing with simplified mounting system

FEATURES OF HOUSING

41 mm
150 mm
46 mm

TECHNICAL FEATURES

Unit of measurement
Measuring range
Accuracy*
Type of sensor
Life-time of the sensor
Response time
Resolution
Type of fluid
Conditions of use (°C/%RH/m)
Storage temperature
*All the accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for measurements carried out in the same conditions, or carried out with calibration compensation.

PART NUMBER

To order, just add the codes to complete the part number :
CO110
Power supply / Output
A : Active – 24 Vac/Vdc – 0-10 V
P : Passive – 16/30 Vdc – 4-20 mA
90 mm
Ambient model
Duct model
ppm
From 0 to 500 ppm
±3 ppm or 3% of the measured value
Electrochemical sensor
5 years
T63 = 35 s
0.1 ppm
Air and neutral gas
From 0 to +50 °C. In non-condensing condition. From 0 to 2000 m.
From -10 to +70 °C
Display
O : with display
N : without display
Material : ABS V0
Protection :
Display : LCD 10 digits. Size : 50 x 17 mm
Height of digits : Value : 10 mm ; Unit : 5 mm
90 mm
Cable gland
maximum
Weight : 138 g (ambient model) ; 150 g (duct model)
Type of probe
A : Duct
S : ambient
- duct model : IP65
- ambient model : IP20
(only for duct model)
Example : CO110-POA
CO transmitter, 4-20 mA passive transmitter, with display
and duct probe
: for cables Ø 8 mm

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CO 110 and is the answer not in the manual?

Questions and answers

Summary of Contents for Kimo CO 110

  • Page 1 CO transmitter CO 110 KEY POINTS - Range from 0 to 500 ppm - 0-10 V active output, power supply 24 Vac/Vdc (3-4 wires) or 4-20 mA output, passive loop, power supply from 16 to 30 Vdc (2 wires) - ABS V0 housing, IP65 (depending on model), with or without display - “¼...
  • Page 2: Technical Specifications

    TECHNICAL SPECIFICATIONS Output / Power supply - active 0-10 V (power supply 24 Vac/Vdc ± 10%), 3-4 wires - passive loop 4-20 mA (power supply 16/30 Vdc), 2 wires - Common mode voltage <30 VAC - maximum load : 500 Ohms (4-20 mA) / minimum load : 1 K Ohms (0-10 V) Consumption 2 VA (0-10 V) or 0.6 VA (4-20 mA) European directives...
  • Page 3 For CO110-P models with 4-20 mA output – passive : Power supply Display/regulator/PLC 16-30 Vdc active type Display/regulator/PLC passive type 2 wires 2 wires 16-30 Vdc 2 wires SETTINGS AND USE OF THE TRANSMITTER Configuration ➢ To configure the transmitter, it must not be energized. Then you can make the required settings thanks to the DIP switches as shown on the drawing below.
  • Page 4: Options And Accessories

    Please always use the device in accordance with its intended use and within parameters described in the technical features in order not to compromise the protection ensured by the device. Once returned to KIMO, required waste collection will be assured in the respect of the environment in accordance with European guidelines relating to WEEE.

Table of Contents