Technical Data - Siemens M-bus Level Converter/Repeater 250 Manual

Meters and energy cost allocation

Advertisement

Technical data

Power supply
Operating voltage
AC frequency
Power consumption
Maximum power consumption
Power consumption level converter (in series)
Internal fuse
Fusing of supply lines
Connections
M-bus master (terminals 9 and 10 on the level
converter)
M-bus slave (terminals 1 and 2 on the level converter)
Vin LC / Vout LC (terminals
11 and 12 on the level converter) /
(terminals 4 and 5 on the power supply)
Vout 24 Vdc (terminals 6 and 7 on the power supply)
Interface
RS-232 interface (terminals A, B, and C
level converter)
RS-485 interface (terminal D, E, and F on the level
converter)
M-bus master
Reference standard
Baud rate
Max. number of M-bus devices per level converter
Max. number of M-bus devices per level converter
14
Smart Infrastructure
AC 110...240 V
47...63 Hz
6 W + 0.07 W for each connected M-bus device
45 W, 45 VA
Vout: DC 24 V, max. 15 VA
≤3 mA (2 M-bus loads)
PTC resistance and varistor
Circuit breaker
or
Power supply with current limitation at 10 A
Connections for M-bus devices
and
Connections for the following repeater
Galvanically isolated connections to the M-bus web
server or to the previous master level converter if the
level converter is used as repeater.
Power supply for level converter/repeater
DC 24 V, max. 15 VA
Galvanically isolated connections to connect to PC/data
logger as master:
Connect to a PC:
Terminal A: TX (PC/data logger receiving line)
Terminal B: RX (PC/data logger transmission
line)
Terminal C: GND (interface reference voltage)
Connection to M-bus web server WTV676..:
Terminal 3[A] RS-232 with terminal 1[A] web
server
Terminal 4[B] RS-232 with terminal 2[B] web
server
Terminal 5[C] RS-232 with terminal 3[C] web
server
Non-isolated connection for connecting to a PC
Connections to connect to PC/data logger as
master:
Terminal D: REF (interface reference voltage)
Terminal E: D+ (Receive/transmission line
potential +)
Terminal F: D- (Receive/transmission line
potential -)
EN13757-2 (physical layer)
300 bps...9600 bps
250 (simple M-bus loads)
250 simple M-bus loads
Max. 13 A, type B, C, D
per EN 60898
A6V11742346_en--_a
2019-10-01