Creating An As Program - Siemens SITOP PSU8200 Manual

Integration of a sitop 24 v power supply in simatic pcs 7
Hide thumbs Also See for SITOP PSU8200:
Table of Contents

Advertisement

5 Uninterruptible 24 V power supply
5.1.3

Creating an AS program

The procedure is as follows:
1. Drag process tag type "UPS1600" to the desired folder in the technological
hierarchy and rename it. (1)
Fig. 5-7
2. Open the plan and carry out the following modifications:
Interconnect input "PV_In" to the first input address of the UPS1600. If you have
used the standard symbols, the symbol is called "IBxxx_Input voltage" (2).
Rename the monitoring block to match its use (3).
Fig. 5-8
3. Compile the AS program and update the view of the CFC plan.
4. Load the program into the automation system.
Integration of a SITOP 24 V Power Supply in PCS 7
Entry ID: 109481908,
V1.0,
2
04/2016
1
3
29