Configuring The Hardware Configuration - Siemens SITOP PSU8200 Manual

Integration of a sitop 24 v power supply in simatic pcs 7
Hide thumbs Also See for SITOP PSU8200:
Table of Contents

Advertisement

4 Redundant 24 V DC power supply
4.1

Configuring the hardware configuration

You do not configure the hardware of the power supply and the of the redundancy
module in the SIMATIC Manager. You configure the AS and the external
peripherals according to the PCS 7 standard. To monitor the power supply units
and the redundancy module, the signal contacts are each connected to one of the
digital inputs of the external peripherals and symbolized appropriately in the
hardware configuration.
The procedure is as follows:
1. In SIMATIC Manager, open the hardware configuration of the automation system.
2. Highlight the digital input assembly of the external peripherals (1) and choose
menu command "Edit > Symbols...".
3. Enter an appropriate symbolic name (2) for the inputs that are connected to the
power supply units and the redundancy module.
4. Click on "OK" to confirm your changes.
5. Compile and load the changed hardware configuration.
Fig. 4-2
Integration of a SITOP 24 V Power Supply in PCS 7
Entry ID: 109481908,
V1.0,
1
04/2016
2
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop pse202uSitop psu8600Sitop pse200uSitop ups1600

Table of Contents