For moving the switch and servicing the modules, make sure the width of the aisle in the equipment
room is at least 0.8 m (2.62 ft).
The equipment room is at least 3 m (9.84 ft) high.
Reserve at least 0.8 m (2.62 ft) of clearance between the rack and walls or other devices.

Rack-mounting

To mount the switch in a rack, adhere to the following requirements:
Use a four-post 19 inch standard rack.
The distance between the left and right rack posts is 465 mm (18.31 in).
Figure 20 Rack width
Make sure the available space between the front rack post and the outer edge of the front rack door
is greater than 180 mm (7.09 in) and the depth of the rack (distance between the front and back
doors) is greater than 800 mm (31.50 in).