SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) – 03.2006 Edition
10.2 NCK safety alarms for Sinumerik 840D sl
Mode group not ready
Channel not ready
NC start inhibit in this channel
Interface signals are set
Alarm display
NC stop for alarm
Check the module in the S7 PROFIBUS configuration
Switch control system OFF and ON again.
PROFIsafe: F module MD %1[%2] – MD %3[%4]: Double
PROFIsafe address
assignment of the
%1 = MD name 1
%2 = MD field index 1
%3 = MD name 2
%4 = MD field index 2
In the NCK MD or in the S7 F parameters, the same PROFIsafe
address has been parameterized for the F modules parameterized in
the specific machine data. This means that a clear communications
relationship between the F master and F slave is not possible.
Mode group not ready
Channel not ready
NC start inhibit in this channel
Interface signals are set
Alarm display
NC stop for alarm
Check and correct the S7 F parameterization and NCK-MD.
Switch control system OFF and ON again.
Diagnostics