Appendix 3 - Selection Of Cables And Accessories - janitza SVG Series User Manual

Power controller
Table of Contents

Advertisement

Appendix 3 – Selection of cables and accessories
Nominal current
Phase cross section, mm²
Phase line N, mm²
PE cable, mm²
Power terminal screws
PE terminal screw
Circuit breaker rated
current
CT line
CT ratio range
Note
Note:
1. If the current of the fundamental oscillation represents the main portion of the total
current (fundamental oscillation + harmonic), the wire cross section of the N-conductor
should be 3 times larger than the phase conductor cross section.
2. The CT ratio should be selected to be 1.5 to 4 times that of the maximum load current.
3. The rated current of the circuit breaker should be selected to be 1.2 times the rated
capacity of the SVG, or more.
75 A
25 mm²
35 mm²
16 mm²
M8
M6
100 A
Less than 15 m: RVVSP 2×2.5 mm²; 15 m - 30 m: RVVSP 2×4 mm²;
Over 30 m: Contact Janitza
150:5 to 10,000:5
If there are certain requirements concerning the cable temperature,
the specification of the cable must be enhanced
145 A
50 mm²
70 mm²
16 mm²
M8
M6
200 A
SVG 50/100
79