8.2.3 The "Settings" button

"SYSTEM"
• The "SYSTEM" button in the menu bar takes you to the Settings menu.
• The parameter settings are password protected. Enter the user password (see page 3)
and confirm it with Confirm.
• Set the Operation Mode, Comp. Rate, Comp. Mode, Power On Mode,
CT Location, Slave Module Quantity and Total Capacity.
Operation Mode:
Q: Power factor correction
B: Compensation of imbalance
Auto-aging: Internal use
Note:
"Operation Mode" in the System settings Menu (Figure 4-31):
The 6 "Operating modes" can be read out.
• Mode 0 "Harmonics" of the 7-inch monitor is the equivalent of mode 0 "Harmonics
Comp." on the 4.3-inch monitor.
• The other modes are identical to the operating modes listed in section 8.1.3 under "Pa-
rameter Settings".
Target Power Factor: Set the grid power factor (cos φ) – setting range: -1 to 1.
Comp. Rate: Compensation rate setting range: 0 to 1, 1 for 100%.
Total Capacity: Total capacity (sum of all modules)
Comp mode: Calculation methods "Intelligent", "Sequential" and "All"
CT ratio: Load current transformer ratio – the setting value must correspond to the settings
of the external CT – setting range: 150 to 30,000 (for example 500 means 500:5)
Power On Mode: Manual or automatic
Slave Module Quantity: Quantity of slave modules
Grid Vol. Adjust: Disable or Enable is configurable, voltage compensation to the value of
the target voltage
Target Vol: Target voltage
PT Ratio: Voltage transformer ratio
Default value: 1.0, means 1:1, range is 0.1 to 25.
CT Location: Current transformer position – load or grid side
Further system settings can be displayed and set on the following pages.
64
Figure 4-31 System Settings menu