6.9
Burner flame goes out during operation
If the flame accidentally goes out during operation, the control
box carries out a recycle (i.e. it repeats the start-up phase once,
and makes a further ignition attempt).
6.10
Stopping of the burner
The burner can be stopped by:
intervening on the disconnecting switch of the electrical sup-
ply line, located on the boiler panel;
working on the switch " 0-AUTO " of Fig. 34;
removing the transparent protection that covers the Operator
Panel, after loosening the relative screw, and using the
panel itself according to.
6.11
Final checks (with burner operating)
Open the thermostat/pressure switch TL
Open the thermostat/pressure switch TS
Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
Turn the air pressure switch to the maximum end of scale
position.
Switch off the burner and disconnect the voltage.
Disconnect the minimum gas pressure switch connector.
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
WARNING
Start-up, calibration and operation of the burner
If the flame is still absent, the control box goes into lockout.
The burner must stop
The burner must stop in lockout
The burner must not start
33
GB
Tab. K
20085953