5.6

Operation

Once the start-up cycle is completed, the servomotor command
moves on to the thermostat/pressure switch TR that controls the
pressure or the temperature in the boiler.
 If the temperature or the pressure is low, the burner progres-
sively increases the output as far as the MAX value.
 If the temperature or the pressure increases, the burner pro-
gressively reduces the output as far as the MIN value. The
sequence repeats endlessly.
5.7

Motor lockout

If the motor does not start, it could be because of a thermal relay
intervention due to its incorrect calibration or problems with the
motor or the main power supply, to release press the button of the
thermal relay, see "Calibration of the thermal relay" on
page 31.
5.8

Ignition failure

If the burner does not switch on, there is a lockout within 3s of the
electrical supply reaching the gas valve.
It may be that the gas does not arrive at the combustion head
within the safety time of 3s.
In this case increase gas ignition flow rate. The arrival of gas to
the pipe coupling is displayed on the pressure gauge, as shown
in (Fig. 38 on page 42).
5.9

Burner flame goes out during operation

If the flame should go out during operation, the burner will lockout
within 1 s.
20205911
Start-up, calibration and operation of the burner
 The burner stops when the heat request is less than the heat
supplied by the burner at MIN output.
 The thermostat/pressure switch TL opens, the flame control
carries out the switching off phase.
 The air damper closes completely to reduce heat losses to a
minimum.
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row.
If the burner locks out for a third time, contact the
WARNING
customer service.
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
DANGER
manual and in compliance with the standards and
regulations of current laws.