Burner Categories; Technical Data; Electrical Data - Riello RS BLU Series Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

4.3

Burner categories

Country of destination
AT, CH, CZ, DK, EE, FI, GR, HU, IS, IT, LT, NO, SE, SI, SK
ES, GB, IE, PT
4.4

Technical data

Model
Output
(1)
Fuel
Gas pressure at max. output
- Gas: G20 / G25
- Gas: G31
Operation
Standard applications
Ambient temperature
Combustion air temperature
Noise levels
Sound pressure
(3)
Sound power
Weight
(1) Reference conditions: Room temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m above sea level.
(2) Pressure on the pressure switch socket (Fig. 33) with zero pressure in the combustion chamber and at maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
power is evaluated, in line with the regulations, on a spherical surface centred on the burner and with a radius of 1 metre.
4.5

Electrical data

Model
Main electrical supply
Control circuit power supply
Fan motor IE2
Ignition transformer
Absorbed electrical power
Protection level
20085953
Technical description of the burner
BE
LV
CY, MT
BE
LU, PL
DE
FR
NL
RS 120/EV BLU
Max.
kW
600 ÷ 1300
Mcal/h
516 ÷ 1118
Min.
kW
Mcal/h
Natural gas: G20 (methane gas) G21 - G22 - G23 - G25 - G31
mbar
(2)
22.5 / 33.6
Intermittent (min. 1 stop in 24 hours)
Two progressive or modulating stages with kit (see ACCESSORIES)
°C
°C max
dB(A)
kg
RS 120/EV BLU
3 ~ 400V +/-10% 50Hz
1N ~ 230V +/-10% 50Hz
Hz
50
rpm
2860
V
230-400
kW
2.2
A
7.6 - 4.4
V1 - V2
I1 - I2
kW max
RS 160/EV BLU
930 ÷ 1860
800 ÷ 1600
300
258
17.7 / 26.4
19.6
Boilers: water. steam. diathermic oil
78.5
89.5
83
RS 160/EV BLU
3 ~ 400V +/-10% 50Hz
1N ~ 230V +/-10% 50Hz
60
50
3500
2900
265 - 460
230-400
2.2
4.5
6.8 - 3.9
15 - 8.7
230 V - 1 x 8 kV
1 A - 20 mA
2.2
8
GB
Gas category
I2E(R)
I2H
I3B/P
I3P
II2E3B/P
II2ELL3B/P
II2Er3P
II2H3B/P
II2H3P
II2L3B/P
RS 200/EV BLU
1380 ÷ 2400
1187 ÷ 2064
300
258
28.0 / 41.8
19.6
0 - 40
60
80.5
91.5
96
RS 200/EV BLU
3 ~ 400V +/-10% 50Hz
1N ~ 230V +/-10% 50Hz
60
50
3460
2920
265 - 460
230-400
4.5
5.5
13.7 - 7.9
18 - 10.4
4.5
IP 44
Tab. B
550
473
19.6
83.0
94.0
101
Tab. C
60
3500
265 - 460
6.6
16.1 - 9.3
6.5
Tab. D