Download Print this page

Controller - Siemens SIPART PS2 6DR5 Series Compact Operating Instructions

Electropneumatic positioners
Hide thumbs Also See for SIPART PS2 6DR5 Series:

Advertisement

Technical data
7.1 All device versions
Construction
With sealant
● Cable glands
Screw-in torque for plastic gland in all enclosures
Screw-in torque for cable gland made of metal/stainless
steel in polycarbonate enclosure
Screw-in torque for metal/stainless steel glands in alumi‐
num/stainless steel enclosure
Screw-in torque for NPT adapter made of metal/stainless
steel in polycarbonate enclosure
Screw-in torque for NPT adapter made of metal/stainless
steel in aluminum/stainless steel enclosure
Screw-in torque for NPT gland in the NPT adapter
NOTE: To avoid damage to the device, the NPT adapter
must be held in place while the NPT gland is screwed into
the NPT adapter.
Tightening torque for union nut made of plastic
Tightening torque for union nut made of metal/stainless
steel
● Pressure gauge block fixing screws
Manometer
● Degree of protection
Manometer made of plastic
Manometer, steel
Manometer made of stainless steel 316
● Vibration resistance
Connections, electrical
● Screw terminals
● Cable gland
Without Ex protection as well as with Ex i
With explosion protection Ex d
Connections, pneumatic
7.1.4

Controller

Controller
Control unit
● Five-point controller
● Dead zone
dEbA = auto
dEbA = 0.1 ... 10 %
Analog-to-digital converter
60
6 Nm (4.4 ft lb)
4 Nm (3 ft lb)
6 Nm (4.4 ft lb)
6 Nm (4.4 ft lb)
8 Nm (5.9 ft lb)
15 Nm (11.1 ft lb)
68 Nm (50 ft lb)
2.5 Nm (1.8 ft lb)
4 Nm (3 ft lb)
6 Nm (4.4 ft lb)
IP31
IP44
IP54
In accordance with DIN EN 837-1
2.5 mm
AWG30-14
2
M20 x 1.5 or 1/2-14 NPT
Ex d-certified M20 x 1.5; 1/2-14 NPT or M25 x 1.5
Female thread G¼ or ¼-18 NPT
Adaptive
Adaptive
Can be set as fixed value
Compact Operating Instructions, 09/2019, A5E03436620-AE
SIPART PS2 (6DR5...)

Hide quick links:

Advertisement

loading