Manual Initialization Of Part-Turn Actuators - Siemens SIPART PS2 6DR5 Series Compact Operating Instructions

Electropneumatic positioners
Hide thumbs Also See for SIPART PS2 6DR5 Series:

Advertisement

Commissioning
5.8 Canceling initialization
5. Start the initialization process. To do this, press the
display shows the following:
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN 1" to "RUN 5" are shown in the lower
line on the display. The initialization process depends on the actuator used, and takes up to
15 minutes.
6. The following display indicates that the automatic initialization is complete. The total angle
of rotation of the actuator is shown on the upper line on the display:
5.7.3

Manual initialization of part-turn actuators

See detailed operating instructions for information on manual initialization of part-turn
actuators.
5.8
Canceling initialization
1. Press the
– Canceling automatic initialization: the display shows "INITA".
– Canceling manual initialization: the display shows "INITM".
The positioner is in the "Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
The software version is displayed.
After releasing the
initialized.
52
button.
button, the positioner is in "P manual mode". The positioner is not
button for at least 5 seconds until the
button for at least 5 seconds.
Compact Operating Instructions, 09/2019, A5E03436620-AE