1MRS757464 C
Section 2
2.1
2.2
REM611
Point List Manual
Modbus data mappings
Overview
This document describes the Modbus data points and structures available in the IED.
The point list describes a superset of all data available through the standard
configuration/s including the optional functionalities.
The majority of the Modbus data points are valid for all standard configurations. Some
data points are standard configuration or optional application dependent and thus not
available in each IED. The unavailable, that means unused, data points always return
value 0 when they are read. The configuration dependent and optional data do not
overlap.
Supported functions in REM611
Table 2:
Supported functions
Function
Protection
Three-phase non-directional overcurrent protection, low stage
Three-phase non-directional overcurrent protection, instantaneous
stage
Non-directional earth-fault protection, low stage
Non-directional earth-fault protection, high stage
Negative-sequence overcurrent protection for machines
Loss of load supervision
Motor load jam protection
Motor start-up supervision
Phase reversal protection
Thermal overload protection for motors
Circuit breaker failure protection
Master trip
Control
Circuit-breaker control
Emergency start-up
Condition monitoring and supervision
Trip circuit supervision
Table continues on next page
Section 2
Modbus data mappings
IEC 61850
A
ME/C101
PHLPTOC
1
PHIPTOC
1
EFLPTOC
1)
1
EFHPTOC
1)
1
MNSPTOC
2
LOFLPTUC
1
JAMPTOC
1
STTPMSU
1
PREVPTOC
1
MPTTR
1
CCBRBRF
1
TRPPTRC
1
CBXCBR
1
ESMGAPC
1
TCSSCBR
2
11